Product Information
PV Modules | |
Parameter | |
Testing Condition | STC |
Maximum Power(Pmax/W) | 620W |
Open Circuit Voltage(Voc/V) | 49.55 |
Short Circuit Current(lsc/A) | 15.93 |
Voltage at Maximum Power(Vmp/V) | 41.06 |
Current at Maximum Power(lmp/A) | 15.10 |
Module Efficiency(%) | 22.95 |
Adopting the 182*210mm N-Type TOPCon cells with the highest efficiency; Mechanical load tests including wind load 2400Pa and snow load 5400Pa done by TUV; Ensure the attenuation probability caused by PID phenomenon is minimized; Strict salt spray and ammonia corrosion test by TUV.
Lithium Battery | |
Parameter | |
Nominal Capacity | 280Ah |
Nominal Voltage | 716.8V |
Max.Charging Current | 140A |
Max.Discharging Current | 140A |
Quick Customization of Electricity; Easy Installation Flexible Expansion; Emergency-Backup and Off-Grid Functionality; Safety first Smart BMS system.
Inverter | |
Parameter | |
Model | MPS0050 |
Dimension WxDxH (mm) | 800 x 800 x 1900 |
AC(on-grid) | |
Rated power | 50kW |
Rated voltage | 208V High-legDelta with split phase(Opt) |
Rated current | 139A |
Rated frequency | 50/60Hz |
THDi | <3% |
Power factor | 1lagging-1leading( Settable ) |
AC connection | 3W/N/PE/3W/N/PE Delta(Opt) |
AC(off-grid) | |
Rated power | 50kW |
Rated voltage | 208V High-legDelta with split phase(Opt) |
Rated current | 139A |
THDU | ≤1% linear; or≤5% nonlinear |
Overload capability | 110% long-term |
PV | |
MAX PV power | 60/120kW |
MPPT voltage range | 320~850V |
Battery | |
Battery voltage range | 320~850 |
Max. charging power (kW) | 60/120 |
General data | |
Net weight (kg) | 720/750 |
Operation temperature (℃) | -30 ~ 55 |
Relative humidity | 0 ~95% non-condensing |
Ingress protection | IP20 |
Noise emission (dB) | <70 |
Operating altitude | 5,000m(>3,000 Derating) |
Cooling | Air Cooling |
Display and communication | |
Display | LCD touch-screen |
BMS communication | RS485, CAN |
EMS communication | RS485, TCP/IP |
Certificates | EN62109-1/-2, EN62477-1, EN61000-6-2, EN61000-6-4, South Africa NRS097-2-1:2017, Pakistan & India IEC61727, IEC62116, IEC 61683 |
Various working modes can be set flexibly; Seamless transfer between on and off grid; Perfect protection function to protect inverters and batteries; Integrated design to support loads, batteries, power grids, diesel generators and PV be connected.